Distribution transformers covered by this standard are defined in the Code of Federal Regulations, 10 CFR 431.192. The three types of distribution transformers covered by the standard: low-voltage dry-type, liquid-immersed, and medium-voltage, dry-type distribution transformers. The full standard can be found in the Code of Federal Regulations, 10 CFR 431.196. This information is also in the Electronic Code of Federal Regulations.
The efficiency of a low-voltage dry-type distribution transformer manufactured on or after January 1, 2007, shall be no less than that required for their kVA rating in the table below. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Table 1. Energy Conservation Standards for Low-Voltage Dry-Type Distribution Transformers
Single phase |
Three phase |
kVa |
Efficiency (%)1 |
kVa |
Efficiency (%)1 |
15 |
97.7 |
15 |
97.0 |
25 |
98.0 |
30 |
97.5 |
37.5 |
98.2 |
45 |
97.7 |
50 |
98.3 |
75 |
98.0 |
75 |
98.5 |
112.5 |
98.2 |
100 |
98.6 |
150 |
98.3 |
167 |
98.7 |
225 |
98.5 |
250 |
98.8 |
300 |
98.6 |
333 |
98.9 |
500 |
98.7 |
|
|
750 |
98.8 |
|
|
1000 |
98.9 |
1 Efficiencies are determined at the following reference conditions: (1) for no-load losses, at the temperature of 20°C, and (2) for load-losses, at the temperature of 75°C and 35 percent of nameplate load. (Source: Table 4–2 of National Electrical Manufacturers Association (NEMA) Standard TP–1–2002, "Guide for Determining Energy Efficiency for Distribution Transformers.")
The efficiency of a liquid-immersed distribution transformer manufactured on or after January 1, 2010, shall be no less than that required for their kVA rating in the table below. Liquid-immersed distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Table 2. Energy Conservation Standards for Liquid-Immersed Distribution Transformers
Single phase |
Three phase |
kVa |
Efficiency (%) |
kVa |
Efficiency (%) |
10 |
98.62 |
15 |
98.36 |
15 |
98.76 |
30 |
98.62 |
25 |
98.91 |
45 |
98.76 |
37.5 |
99.01 |
75 |
98.91 |
50 |
99.08 |
112.5 |
99.01 |
75 |
99.17 |
150 |
99.08 |
100 |
99.23 |
225 |
99.17 |
167 |
99.25 |
300 |
99.23 |
250 |
99.32 |
500 |
99.25 |
333 |
99.36 |
750 |
99.32 |
500 |
99.42 |
1000 |
99.36 |
667 |
99.46 |
1500 |
99.42 |
833 |
99.49 |
2000 |
99.46 |
|
|
2500 |
99.49 |
Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the DOE Test-Procedure. 10 CFR Part 431, Subpart K, Appendix A.
The efficiency of a medium-voltage dry-type distribution transformer manufactured on or after January 1, 2010, shall be no less than that required for their kVA and BIL rating in the table below. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Table 3: Energy Conservation Standards for Medium-Voltage Dry-Type Distribution Transformers
Single phase |
Three phase |
BIL
kVa
|
20–45 kV efficiency
(%)
|
46–95 kV efficiency
(%)
|
96 kV efficiency
(%)
|
BIL
kVa
|
20–45 kV
efficiency (%)
|
46–95 kV efficiency (%) |
96 kV efficiency (%) |
15 |
98.10 |
97.86 |
|
15 |
97.50 |
97.18 |
|
25 |
98.33 |
98.12 |
|
30 |
97.90 |
97.63 |
|
37.5 |
98.49 |
98.30 |
|
45 |
98.10 |
97.86 |
|
50 |
98.60 |
98.42 |
|
75 |
98.33 |
98.12 |
|
75 |
98.73 |
98.57 |
98.53 |
112.5 |
98.49 |
98.30 |
|
100 |
98.82 |
98.67 |
98.63 |
150 |
98.60 |
98.42 |
|
167 |
98.96 |
98.83 |
98.80 |
225 |
98.73 |
98.57 |
98.53 |
250 |
99.07 |
98.95 |
98.91 |
300 |
98.82 |
98.67 |
98.63 |
333 |
99.14 |
99.03 |
98.99 |
500 |
98.96 |
98.83 |
98.80 |
500 |
99.22 |
99.12 |
99.09 |
750 |
99.07 |
98.95 |
98.91 |
667 |
99.27 |
99.18 |
99.15 |
1000 |
99.14 |
99.03 |
98.99 |
833 |
99.31 |
99.23 |
99.20 |
1500 |
99.22 |
99.12 |
99.09 |
|
|
|
|
2500 |
99.31 |
99.23 |
99.20 |
|
|
|
|
2500 |
99.31 |
99.23 |
99.20 |
Note: BIL means basic impulse insulation level.
Note: All efficiency values are at 50 percent of nameplate rated load, determined according to the DOE Test Procedure. 10 CFR Part 431, Subpart K, Appendix A.
For further guidance or to submit questions related to the implementation of this standard, visit the Guidance and Frequently Asked Questions page.
Amended Standard
Distribution transformers covered by this standard are defined in the Code of Federal Regulations, 10 CFR 431.192. The three types of distribution transformers covered by the standard: low-voltage dry-type, liquid-immersed, and medium-voltage, dry-type distribution transformers. The full standard can be found in the Code of Federal Regulations, 10 CFR 431.196. This information is also in the Electronic Code of Federal Regulations.
The efficiency of a low-voltage dry-type distribution transformer manufactured on or after January 1, 2016, shall be no less than that required for their kVA rating in the table below. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Table 4: Amended Energy Conservation Standards for Low-Voltage Dry-Type Distribution Transformers
Single phase |
Three phase |
kVa |
Efficiency (%) |
kVa |
Efficiency (%) |
15 |
97.70 |
15 |
97.89 |
25 |
98.00 |
30 |
98.23 |
37.5 |
98.20 |
45 |
98.40 |
50 |
98.30 |
75 |
98.60 |
75 |
98.50 |
112.5 |
98.74 |
100 |
98.6 |
150 |
98.83 |
167 |
98.70 |
225 |
98.94 |
250 |
98.80 |
300 |
99.02 |
333 |
98.90 |
500 |
99.14 |
|
|
750 |
99.23 |
|
|
1000 |
99.28 |
Note: All efficiency values are at 35 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under Appendix A to Subpart K of 10 CFR part 431.
The efficiency of a liquid-immersed distribution transformer manufactured on or after January 1, 2016, shall be no less than that required for their kVA rating in the table below. Liquid-immersed distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Table 5: Amended Energy Conservation Standards for Liquid-Immersed Distribution Transformers
Single phase |
Three phase |
kVa |
Efficiency (%) |
kVa |
Efficiency (%) |
10 |
98.70 |
15 |
98.65 |
15 |
98.82 |
30 |
98.83 |
25 |
98.95 |
45 |
98.92 |
37.5 |
99.05 |
75 |
99.03 |
50 |
99.11 |
112.5 |
99.11 |
75 |
99.19 |
150 |
99.16 |
100 |
99.25 |
225 |
99.23 |
167 |
99.33 |
300 |
99.27 |
250 |
99.39 |
500 |
99.35 |
333 |
99.43 |
750 |
99.40 |
500 |
99.49 |
1000 |
99.43 |
667 |
99.52 |
1500 |
99.48 |
883 |
99.55 |
2000 |
99.51 |
|
|
2500 |
99.53 |
Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under Appendix A to Subpart K of 10 CFR part 431.
The efficiency of a medium- voltage dry-type distribution transformer manufactured on or after January 1, 2016, shall be no less than that required for their kVA and BIL rating in the table below. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Table 6: Amended Energy Conservation Standards for Medium-Voltage Dry-Type Distribution Transformers
Single phase |
Three phase |
BIL* kVa |
20–45 kV efficiency (%) |
46–95 kV efficiency (%) |
96 kV efficiency (%) |
BIL kVa |
20–45 kV efficiency (%) |
46–95 kV efficiency (%) |
96 kV efficiency (%) |
15 |
98.10 |
97.86 |
- |
15 |
97.50 |
97.18 |
- |
25 |
98.33 |
98.12 |
- |
30 |
97.90 |
97.63 |
- |
37.5 |
98.49 |
98.30 |
- |
45 |
98.10 |
97.86 |
- |
50 |
98.60 |
98.42 |
- |
75 |
98.33 |
98.13 |
- |
75 |
98.73 |
98.57 |
98.53 |
112.5 |
98.52 |
98.36 |
- |
100 |
98.82 |
98.67 |
98.63 |
150 |
98.65 |
98.51 |
- |
167 |
98.96 |
98.83 |
98.80 |
225 |
98.82 |
98.69 |
98.57 |
250 |
99.07 |
98.95 |
98.91 |
300 |
98.93 |
98.81 |
98.69 |
333 |
99.14 |
99.03 |
98.99 |
500 |
99.09 |
98.99 |
98.89 |
500 |
99.22 |
99.12 |
99.09 |
750 |
99.21 |
99.12 |
99.02 |
667 |
99.27 |
99.18 |
99.15 |
1000 |
99.28 |
99.20 |
99.11 |
833 |
99.31 |
99.23 |
99.20 |
1500 |
99.37 |
99.30 |
99.21 |
|
|
|
|
2000 |
99.43 |
99.36 |
99.28 |
|
|
|
|
2500 |
99.47 |
99.41 |
99.33 |
BIL means basic impulse insulation level
Note: All efficiency values are at 50 percent of nameplate rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under Appendix A to Subpart K of 10 CFR part 431.
After a regulatory action has been completed, Executive Order 12866 requires agencies to identify the substantive changes between the draft submitted to Office of Information and Regulatory Affairs (OIRA) for review and the action subsequently announced, and to identify those changes made at the suggestion or recommendation of OIRA. The document below provides more information: