Model Contract Language for Water-Cooled Chillers

In accordance with the Energy Policy Act of 2005, the Federal Acquisition Regulations Section 23, and Presidential Executive Order 13123 the vendor shall provide water-cooled chillers that meet or exceed the latest Federal Energy Management Program (FEMP) energy-efficiency purchasing specifications. Refer to the FEMP Web site at www.eere.energy.gov/femp/procurement/ to obtain proper sizing and cost-effectiveness data, operating tips and other important information.

Performance Requirements for Water-Cooled Chillers – Effective 11/2003
Part Load Optimized Chillers
Compressor Type and Capacity Recommended IPLV (kW/ton)
Centrifugal (150 to 200 ton) 0.52 kW/ton or less
Centrifugal (300 to 2,000 ton) 0.45 kW/ton or less
Rotary Screw (> 300 ton) 0.49 kW/ton or less
Full Load Optimized Chillers
Compressor Type and Capacity Recommended Full Load
Centrifugal (150 to 200 ton) 0.59 kW/ton or less
Centrifugal (300 to 2,000 ton) 0.56 kW/ton or less
Rotary Screw (> 300 ton) 0.64 kW/ton or less

This language is available for download (MS DOC 48 KB).