How to Buy an Energy-Efficient Distribution Transformer

ENERGY STAR Qualified Products

Information about energy-efficient distribution transformers in this section includes the following:

Efficiency Recommendation
Cost-Effectiveness Example
Where to Find
 Buyer Tips
Safety
For More Information

Also provided is a portable document format version of How to Buy an Energy-Efficient Distribution Transformer (PDF 127 KB, 2 pp). Download Adobe Reader.

Efficiency Recommendationa
Single Phase Percent Efficiency
Rated Capacity (kVA) Low Voltageb Medium Voltagec
Recommended Level Recommended Level (Dry) Recommended Level (Liquid)d
10 98.3 or more
15 97.7 or more 97.6 or more 98.5 or more
25 98.0 or more 97.9 or more 98.7 or more
37.5 98.2 or more 98.1 or more 98.8 or more
50 98.3 or more 98.2 or more 98.9 or more
75 98.5 or more 98.4 or more 99.0 or more
100 98.6 or more 98.5 or more 99.0 or more
167 98.7 or more 98.7 or more 99.1 or more
250 98.8 or more 98.8 or more 99.2 or more
333 98.9 or more 98.9 or more 99.2 or more
500 99.0 or more 99.3 or more
667 99.0 or more 99.4 or more
833 99.1 or more 99.4 or more
Three Phase Percent Efficiency
15 97.0 or more 96.8 or more 98.0 or more
30 97.5 or more 97.3 or more 98.3 or more
45 97.7 or more 97.6 or more 98.5 or more
75 98.0 or more 97.9 or more 98.7 or more
112.5 98.2 or more 98.1 or more 98.8 or more
150 98.3 or more 98.2 or more 98.9 or more
225 98.5 or more 98.4 or more 99.0 or more
300 98.6 or more 98.5 or more 99.0 or more
500 98.7 or more 98.7 or more 99.1 or more
750 98.8 or more 98.8 or more 99.2 or more
1000 98.9 or more 98.9 or more 99.2 or more
1500 99.0 or more 99.3 or more
2000 99.0 or more 99.4 or more
2500 99.1 or more 99.4 or more

a Energy efficiency of distribution transformers is defined by NEMA's Standard Publication TP-1 (see "For More Information") as output kVA divided by the sum of output kVA plus losses, at a specified percent load and reference temperature.
b Low voltage transformers have a primary voltage of 1200 volts or less; efficiency is measured at 35% of nameplate load, at 75°C.
c Medium voltage transformers have a primary voltage greater than 1200 volts; efficiency is measured at 50% of nameplate load, at 75°C for dry-type transformers and 85°C for liquid-filled.
d Liquid-filled transformers typically use oil as a combination coolant and insulating medium. They are generally higher in efficiency but are most frequently installed outside.

Back to Top

Cost-Effectiveness Example
1500 kVA, Three Phase, Medium Voltage Dry-Type
Performance Base Model Recommended Level
Efficiency 98.6% 99.0%
Annual Energy Lossa 91,380 kWh 66,360 kWh
Annual Energy Loss Cost $5,480 $3,980
Lifetime Energy Loss Cost $74,000 $54,400
Lifetime Energy Cost Savings $20,500
25 kVA, Single Phase, Low Voltage
Efficiency 96.7% 98.0%
Annual Energy Lossa 2,600 kWh 1,570 kWh
Annual Energy Loss Cost $156 $94
Lifetime Energy Loss Cost $2,130 $1,290
Lifetime Energy Cost Savingsb $11,000 $16,000

a Annual energy loss is based on 50% of nameplate load in the medium voltage example (top), and 35% of nameplate load in the low voltage example (bottom).
b Lifetime energy cost savings is the sum of the discounted value of annual energy cost savings based on average usage and an assumed transformer life of 25 years. Future electricity price trends and a discount rate of 3.4% are based on Federal guidelines (effective from April 2000 to March 2001). The assumed electricity price is $0.06/kWh, the Federal average electricity price in the U.S.

Using the Cost-Effectiveness Table: In the example shown above, a 1500 kVA, three phase, medium voltage transformer at the recommended efficiency level of 99.0% is cost-effective if its purchase price is no more than $22,300 above the price of the base model. Similarly in the 25 kVA, single phase, low voltage example, the Recommended model, with an efficiency of 98.0%, is cost-effective if its purchase price is no more than $900 above the price of the base model.

EPA provides software to assist in evaluating the cost-effectiveness of transformers for both new and replacement applications (see For More Information).

Back to Top

Where to Find Energy-Efficient Distribution Transformers

The Federal supply source for transformers is the General Services Administration (GSA). GSA offers transformers through Schedule 61-V(B), Power Distribution Equipment. Whether you buy from GSA, or use a commercial supplier or contractor (e.g., an A&E firm), be sure to specify a transformer that meets the efficiency recommendation for that capacity and type.

The efficiency levels in this recommendation are the same as those in NEMA's TP-1 standard. The Consortium for Energy Efficiency (CEE) (see For More Information) and the EPA/DOE program identify low-voltage distribution transformers that meet the efficiency criteria specified in this Recommendation and TP-1.

Back to Top

Buyer Tips

Many types of modern office equipment and devices (personal computers, printers, copiers, fax machines, electronic lighting ballasts) and some industrial equipment (adjustable speed motor drives) impose non-linear loads, which can introduce power wave form distortion. If your transformer serves equipment such as these, consider using a "K-rated" or "drive isolation" transformer designed for specific types of non-linear loads. Simply replacing an existing transformer with a standard unit rated at a higher kVA level is generally not a good approach for these applications. Both first cost and operating cost are frequently higher with larger capacity standard units, which are not designed to accommodate harmonics and other problems imposed by non-linear loads.

Back to Top

Safety

Safety codes require that indoor transformer installations meet stringent fire-protection and spill containment conditions. Some "less-flammable liquid-filled" transformers can meet code requirements for indoor uses when applicable fire protection and spill containment conditions are met.

Back to Top

For More Information

  • National Electrical Manufacturers Association (NEMA) publishes Standards Publication TP-1-1996, Guide for Determining Energy Efficiency for Distribution Transformers.
    Phone: (800) 854-7179
  • Consortium for Energy Efficiency (CEE) provides information on transformers that meet this recommendation and utility programs promoting low-voltage transformers.
    Phone: (617) 589-3949
  • Environmental Protection Agency (EPA) has transformer model listings. EPA also provides computer software that performs cost-effectiveness analyses for transformers.
    Phone: (888) 782-7937
  • Lawrence Berkeley National Laboratory provided supporting analysis for this recommendation.
    Phone: (202) 646-7950

Back to Top