U.S. Department of Energy - Energy Efficiency and Renewable Energy

Federal Energy Management Program – Energy-Efficient Products

How to Buy an Energy-Efficient Commercial Unitary Air Conditioner

ENERGY STAR Qualified Products

Information about energy-efficient unitary air conditioners in this section includes the following:

Efficiency Recommendation
Cost-Effectiveness Example
Calculate Costs
How to Select
Sizing
 Heating Options
Technology Options
Installation and Maintenance
Environmental Tips
For More Information

Also provided is a portable document format version of How to Buy an Energy-Efficient Commercial Unitary Air Conditioner (PDF 181 KB, 2 pp). Download Adobe Reader.

Efficiency Recommendation
Product Type and Sizea Recommended Level Best Available
<65 MBtu/h (3 phase) 12.0 SEER or moreb 14.5 SEER
65 - 135 MBtu/h 11.0 EER or more
11.4 IPLV or more
11.8 EER
13.0 IPLV
>135 - 240 MBtu/h 10.8 EER or more
11.2 IPLV or more
11.5 EER
13.3 IPLV

a Only air-cooled single-packaged and split system units used in commercial buildings are covered. Water source units are not covered by ENERGY STAR® but look for efficiency ratings that meet or exceed these levels for air source units.
b When operating conditions are often close to rated conditions or in regions where there are high demand costs, look for units with the highest EER ratings that also meet or exceed this SEER.

EER (energy efficiency ratio) is the cooling capacity (in Btu/hour) of the unit divided by its electrical input (in watts) at the Air Conditioning and Refrigeration Institute's (ARI) standard peak rating condition of 95°F.

SEER (seasonal energy efficiency ratio) and IPLV (integrated part-load value) are similar to EER but weigh performance at different (peak and off-peak) conditions during the cooling season.

Back to Top

Cost-Effectiveness Example
120 MBtu/h - 10 Tons
Performance Base Modela Recommended Levelb Best Available
EER / IPLV 8.9 / 9.2 11.0 / 11.4 11.8 / 13.0
Annual Energy Use 19,600 kWh 15,800 kWh 13,800 kWh
Annual Energy Cost $1,170 $950 $830
Lifetime Energy Costc $11,700 $9,500 $8,300
Lifetime Energy Cost Savings $2,200 $3,400

a The integrated part-load value (IPLV) corresponds to an average model meeting the minimum national standard EER of 8.9.
b For illustration only, there may not be an actual model available that just meets both EER and IPLV efficiency criteria.
c Lifetime energy cost is the sum of the discounted (present) value of annual energy costs based on average usage and an assumed air conditioner life of 15 years. Future electricity price trends and a discount rate of 3.3% are based on Federal guidelines (effective from April 2001 to March 2002).

Metric Conversions:
1 Ton = 12,000 Btu/h
1,000 Btu/h = 293 watts
°F = (1.8 * °C) + 32
1 Foot = 30.5 cm

Cost-Effectiveness Assumptions: The cost-effectiveness example assumes annual energy use is based on the standard DOE test procedure for a model with 1,500 equivalent full-load hours per year. The assumed electricity price is $0.06/kWh (including demand charges).

Using the Cost-Effectiveness Table: In the example shown above, a commercial unitary air conditioner with an IPLV of 11.0 is cost-effective if its purchase price is no more than $2,200 above the price of the base model. The best available model, with an IPLV of 13.0, is cost-effective if its price is no more than $3,400 above the price of the base model.

Back to Top

Determine Your Own Project's Cost-Effectiveness

Try the Energy Cost Calculator for Commercial Unitary Air Conditioner (Rooftops) to compare the energy costs for your selection with FEMP-recommended and "Best Available" commerical unitary air conditioners. You can model different scenarios by varying electricity cost, capacity, efficiency, and hours of operation.

Back to Top

How to Select Energy-Efficient Commercial Air Conditioners

For contractor-supplied equipment, specify an ENERGY STAR® labeled model or one that meets or exceeds these recommended levels. In early 2002, the Defense Logistics Agency (DLA) expects to offer highly efficient commercial unitary air conditioners with efficiencies that meet or exceed these recommended levels. DLA will select models through a competitive procurement based on lowest life-cycle cost.

Back to Top

Sizing

Oversizing of air conditioners, besides raising purchase cost, will increase energy use, reduce humidity removal, and shorten product life, all due to excessive on-off cycling ("short-cycling"). The required air conditioner capacity should be determined based on the referenced ASHRAE calculation procedure (see For More Information).

Back to Top

Heating Options

Commercial unitary air conditioners can usually be purchased with several options for heating, including a gas or oil furnace, hot water or steam coils, or electric resistance heating. Heat pump models will use less energy than electric resistance heating (see "How to Buy an Energy-Efficient Commercial Heat Pump").

Back to Top

Technology Options

Many factors (not reflected in the efficiency ratings) can affect the energy performance of a commercial unitary air conditioner. Water source models, which use cooling towers, are generally more efficient than air source models, but have higher first costs and maintenance requirements. Economizers provide "free" cooling by using controllable dampers that bring outside air to cool the space when the outdoor temperature or enthalpy are below the building's return air. When properly controlled and maintained, economizers can decrease energy consumption substantially. Two-speed fans allow for decreased energy use in ventilation-only mode, when neither heating nor cooling is needed. Economizers, two-speed fans and other features have impressive energy-saving capability, but usually requires operation by an appropriate and well calibrated control system.

Back to Top

Installation and Maintenance

Proper installation and maintenance of commercial unitary air conditioners are essential for effective and efficient operation. ACEEE's Guide to Energy-Efficient Commercial Equipment, along with other publications from CEE and PNNL, provides tips on installation and maintenance concerns (see For More Information). Duct losses are a major source of energy waste and comfort problems; make sure ducts are well-sealed.

Back to Top

Environmental Tips

Many of today's commercial unitary air conditioners use HCFC refrigerants and other refrigerants with a low Ozone Depletion Factor (ODF). When retiring an air conditioner that contains CFCs or HCFCs, the Clean Air Act requires that the refrigerant be recovered on-site by a certified technician. For information, contact EPA's hotline at (800) 296-1996.

Back to Top

For More Information

Back to Top