Federal Water Use Indices
FEMP provides water use indices as a guide for Federal agencies. Note that each is a rough estimate of water usage at different types of sites. Your site may vary considerably.
The following indices should be used only to assist in determining baseline data when no other information is available on site water usage.
Water use indices are available for the following facility types:
Conversion factors for the Federal water use indices are also available.
Source: American Water Works Association 1996. Data represents gallons per unit per day.
Commercial
| User | Unit | Range | Typical |
|---|---|---|---|
| Airport | Passenger | 4-5 | 3 |
| Apartment house | Person | 100-200 | 100 |
| Boarding house | Person | 25-50 | 40 |
| Hotel | Guest | 40-60 | 50 |
| Employee | 8-13 | 10 | |
| Lodging house and tourist home | Guest | 30-50 | 40 |
| Motel | Guest | 25-40 | 35 |
| Motel with kitchen | Guest | 25-60 | 40 |
| Laundry (self-service) | Machine | 400-650 | 550 |
| Office | Employee | 8-20 | 15 |
| Public Lavatory | User | 3-6 | 5 |
| Restaurant (including toilet) | |||
| Conventional | Customer | 8-10 | 9 |
| Short-order | Customer | 3-8 | 8 |
| Parking Space | 1-3 | 8-13 | |
| Employee | 2 | 10 | |
| Open Space | |||
| Non-turf | Acre | 785 | |
| Turf | Acre | 1571 | |
Recreational
| User | Unit | Range | Typical |
|---|---|---|---|
| Apartment, resort | Person | 50-70 | 60 |
| Bowling alley | Alley | 150-250 | 200 |
| Camp | |||
| Pioneer type | Person | 15-30 | 25 |
| With toilet and bath | Person | 35-50 | 45 |
| Day, with meals | Person | 10-20 | 15 |
| Day, without meals | Person | 8-18 | 13 |
| Trailer | Trailer | 75-150 | 125 |
| Campground | Person | 20-40 | 30 |
| Country Club | Members | 80-125 | 100 |
| Employee | 10-15 | 50 | |
| Dormitory (bunk house) | Person | 20-45 | 35 |
| Fairground | Visitor | 1-2 | 3 |
| Picnic park with flush toilets | Visitor | 5-10 | 6 |
| Swimming Pool and Beach | Customer | 5-15 | 10 |
| Employee | 8-15 | 10 | |
| Visitor center | Visitor | 4-8 | 5 |
Institutional
| User | Unit | Range | Typical |
|---|---|---|---|
| Assembly hall | Seat | 2-4 | 3 |
| Medical Hospital | Bed | 80-150 | 120 |
| Employee | 5-15 | 10 | |
| Prison | Inmate | 80-150 | 120 |
| Employee | 5-15 | 10 | |
| Rest Home | Resident | 5-120 | 90 |
| Employee | 5-15 | 10 | |
| School, Day | |||
| With cafeteria, gym and showers | Student | 15-30 | 25 |
| With cafeteria only | Student | 10-20 | 15 |
| Without cafe and gym | Student | 5-15 | 10 |
| School, Boarding | Student | 50-100 | 75 |
Conversion Factors for Federal Water Use Indices
Volume conversion
| 1 gallon (gal) | = 8.34 pounds |
| 1 cubic foot (ft3) | = 7.48 gallons |
| 1 unit (Ccf) | = 748 gallons |
| 1 acre-foot (AF) | = 325,851 gallons |
| 1 acre-foot (AF) | = 43,560 cubic feet |
| 1 million gallons/day (MGD) | = 1121 acre feet/year |
Metric conversions
| 1 acre | = .4 hectares |
| 1 gallon | = 3.8 liters |
| 1 cubic foot | = 0.3 cubic meters |